SiBE05-722_A[Applied Models]z Inverter Pair : Cooling Onlyz Inverter Pair : Heat PumpInverter PairFloor / Ceiling Suspended Dual TypeBA-Series

Pagina 2 - BA-Series

Introduction SiBE05-722_Aix1.2 Used IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is de

Pagina 3 - Table of Contents ii

Troubleshooting SiBE05-722_A90 Service DiagnosisTroubleshootingCheck No.06Refer to P.105H9 : Outdoor temperature thermistorJ3 : Discharge pipe thermis

Pagina 4

SiBE05-722_A TroubleshootingService Diagnosis 913.20 Electrical Box Temperature RiseRemote Controller DisplayL3Method of Malfunction DetectionAn elect

Pagina 5 - Table of Contents iv

Troubleshooting SiBE05-722_A92 Service DiagnosisTroubleshooting RK(X)S25/35E2V1B modelsCheck No.06Refer to P.105Check No.07Refer to P.106Check No.09Re

Pagina 6 - 1. Introduction

SiBE05-722_A TroubleshootingService Diagnosis 93Troubleshooting RK(X)S25/35G2V1B, RK(X)S25/35G2V1B9 modelsCheck No.07Refer to P.106Check No.09Refer to

Pagina 7

Troubleshooting SiBE05-722_A94 Service Diagnosis3.21 Radiation Fin Temperature RiseRemote Controller DisplayL4Method of Malfunction DetectionA radiati

Pagina 8

SiBE05-722_A TroubleshootingService Diagnosis 95Troubleshooting RK(X)S25/35E2V1B modelsCheck No.06Refer to P.105Check No.07Refer to P.106Check No.09Re

Pagina 9

Troubleshooting SiBE05-722_A96 Service DiagnosisTroubleshooting RK(X)S25/35G2V1B, RK(X)S25/35G2V1B9 modelsCheck No.07Refer to P.106Check No.09Refer to

Pagina 10 - 1.2 Used Icons

SiBE05-722_A TroubleshootingService Diagnosis 973.22 Output Overcurrent DetectionRemote Controller DisplayL5Method of Malfunction DetectionAn output o

Pagina 11 - List of Functions

Troubleshooting SiBE05-722_A98 Service DiagnosisTroubleshootingCheck No.07Refer to P.106Check No.08Refer to P.106Check No.13Refer to P.108(R12016)Caut

Pagina 12 - 1. Functions

SiBE05-722_A TroubleshootingService Diagnosis 993.23 Refrigerant ShortageRemote Controller DisplayU0Method of Malfunction DetectionRefrigerant shortag

Pagina 13 - — : No Functions

SiBE05-722_AList of Functions 1Part 1List of Functions1. Functions...

Pagina 14 - 4 List of Functions

Troubleshooting SiBE05-722_A100 Service DiagnosisTroubleshootingCheck No.04Refer to P.103Check No.06Refer to P.105(R12015)CautionYESNGNONOYESYESYESNOY

Pagina 15 - Specifications

SiBE05-722_A TroubleshootingService Diagnosis 1013.24 Low-voltage Detection or Over-voltage DetectionRemote Controller DisplayU2Method of Malfunction

Pagina 16 - 1. Specifications

Troubleshooting SiBE05-722_A102 Service DiagnosisTroubleshootingCorrect the power supply.Replace the PM1. (Replace the outdoor unit PCB.)Check for suc

Pagina 17 - 50 Hz, 220 - 230 - 240 V

SiBE05-722_A CheckService Diagnosis 1034. Check4.1 How to Check4.1.1 Electronic Expansion Valve CheckCheck No.04 Conduct the followings to check the e

Pagina 18

Check SiBE05-722_A104 Service Diagnosis4.1.2 Four Way Valve Performance CheckCheck No.05(R11903)NOYESYESNOTurn off the power and turn it on again.Disc

Pagina 19 - 1.2 Heat Pump

SiBE05-722_A CheckService Diagnosis 1054.1.3 Thermistor Resistance CheckCheck No.06 Disconnect the connectors of the thermistors from the PCB, and mea

Pagina 20

Check SiBE05-722_A106 Service Diagnosis4.1.4 Installation Condition CheckCheck No.074.1.5 Discharge Pressure CheckCheck No.08Installation condition ch

Pagina 21

SiBE05-722_A CheckService Diagnosis 1074.1.6 Outdoor Fan System CheckCheck No.09 DC motor4.1.7 Power Supply Waveforms CheckCheck No.10 Measure the pow

Pagina 22 - Connector Wiring Diagram

Check SiBE05-722_A108 Service Diagnosis4.1.9 Power Module CheckCheck No.13Note: Check to make sure that the voltage between (+) and (–) of the diode b

Pagina 23 - 1.1 Indoor Unit

SiBE05-722_A CheckService Diagnosis 1094.1.10 Rotation Pulse Check on the Outdoor Unit PCBCheck No.15 RK(X)S25/35E2V1B, RK(X)S25/35G2V1BMake sure that

Pagina 24 - PCB (2) : Power Supply PCB

Functions SiBE05-722_A2 List of Functions1. FunctionsCategory FunctionsFLKS25/35BAVMBRKS25/35E2V1BFLXS25/35BAVMBRXS25/35E2V1BCategory FunctionsFLKS25/

Pagina 25

Check SiBE05-722_A110 Service Diagnosis4.1.11 Hall IC CheckCheck No.16 1. Check the connector connection.2. With the power on, operation off, and the

Pagina 26 - PCB (2): Main PCB

SiBE05-722_A CheckService Diagnosis 111RK(X)S25/35G2V1B modelsRK(X)S25/35G2V1B9 models(R12411)+~~–4321–+Tester(R12035)Tester–~~+1234–+

Pagina 27 - 1.2.2 RK(X)S25/35G2V1B

SiBE05-722_A112 Removal ProcedurePart 7Removal Procedure1. Indoor Unit...

Pagina 28

SiBE05-722_A Indoor UnitRemoval Procedure 1131. Indoor Unit1.1 Removal of Air Filter / Front GrilleProcedure Warning Be sure to wait 10 minutes or mor

Pagina 29 - 1.2.3 RK(X)S25/35G2V1B9

Indoor Unit SiBE05-722_A114 Removal Procedure2Hold the tab at the center of the air filter frame and pull the air filter forward.3Pull the air filter

Pagina 30

SiBE05-722_A Indoor UnitRemoval Procedure 1152To remove the front grille, unfasten the hooks at 3 locations.4. Remove the side cover.1Remove the side

Pagina 31 - Function and Control

Indoor Unit SiBE05-722_A116 Removal Procedure1.2 Removal of Front PanelProcedure Warning Be sure to wait 10 minutes or more after turning off all powe

Pagina 32 - 1. Main Functions

SiBE05-722_A Indoor UnitRemoval Procedure 1174Unfasten the 3 hooks of the front panel.Caution For ceiling-suspended type, be careful that the front pa

Pagina 33

Indoor Unit SiBE05-722_A118 Removal Procedure1.3 Removal of Horizontal BladeProcedure Warning Be sure to wait 10 minutes or more after turning off all

Pagina 34 - 1.3 Airflow Direction Control

SiBE05-722_A Indoor UnitRemoval Procedure 1191.4 Removal of Signal Receiver Unit / Swing MotorProcedure Warning Be sure to wait 10 minutes or more aft

Pagina 35 - (R12390)

SiBE05-722_A FunctionsList of Functions 3Category FunctionsFLKS25/35BAVMBRKS25/35G2V1BFLXS25/35BAVMBRXS25/35G2V1BCategory FunctionsFLKS25/35BAVMBRKS25

Pagina 36 - 1.5 Program Dry Operation

Indoor Unit SiBE05-722_A120 Removal Procedure1.5 Removal of Discharge GrilleProcedure Warning Be sure to wait 10 minutes or more after turning off all

Pagina 37 - 1.6 Automatic Operation

SiBE05-722_A Indoor UnitRemoval Procedure 1211.6 Removal of Drain PanProcedure Warning Be sure to wait 10 minutes or more after turning off all power

Pagina 38 - 1.7 Thermostat Control

Indoor Unit SiBE05-722_A122 Removal Procedure1.7 Removal of Electrical Box / PCBProcedure Warning Be sure to wait 10 minutes or more after turning off

Pagina 39 - (R11813)

SiBE05-722_A Indoor UnitRemoval Procedure 1234The illustration shows the control PCB.Refer to page 14 for detail.5Disconnect the terminals from the t

Pagina 40 - <Heating>

Indoor Unit SiBE05-722_A124 Removal Procedure6The illustration shows the power supply PCB.Refer to page 14 for detail.2. Remove the electrical box.S

Pagina 41 - POWERFUL

SiBE05-722_A Indoor UnitRemoval Procedure 1251.8 Removal of Fan Rotor / Fan MotorProcedure Warning Be sure to wait 10 minutes or more after turning of

Pagina 42 - 1.11 Other Functions

Indoor Unit SiBE05-722_A126 Removal Procedure3Remove the 2 screws to remove the fan motor fixtures.4Remove the screw to remove the bearing fixture.5Re

Pagina 43 - 2. Function of Thermistor

SiBE05-722_A Indoor UnitRemoval Procedure 1271.9 Removal of Indoor Heat ExchangerProcedure Warning Be sure to wait 10 minutes or more after turning of

Pagina 44 - 3. Control Specification

Indoor Unit SiBE05-722_A128 Removal Procedure4Hook is located on the right side behind the indoor heat exchanger.WarningDo not contaminate any gas (in

Pagina 45 - 3.2 Frequency Control

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1292. Outdoor Unit - RK(X)S25/35E2V1B2.1 Removal of Outer Panels / Fan MotorProcedure Wa

Pagina 46

Functions SiBE05-722_A4 List of FunctionsCategory FunctionsFLKS25/35BAVMBRKS25/35G2V1B9FLXS25/35BAVMBRXS25/35G2V1B9Category FunctionsFLKS25/35BAVMBRKS

Pagina 47 - 3.3.1 Preheating Operation

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A130 Removal Procedure2Remove the 3 screws and lift the top panel.3Remove the drip proof plate.4Disconnect

Pagina 48 - 3.3.4 3-minute Standby

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1316Unfasten the hooks.Pull and remove the front panel.The front panel has 4 hooks.3. R

Pagina 49

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A132 Removal Procedure3Remove the 2 screws and lift the bell mouth to unfasten the hooks.4Remove the bell m

Pagina 50 - 3.5 Input Current Control

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1336Remove the 4 screws and remove the fan motor.M4×167Remove the 2 screws and remove t

Pagina 51 - (R11819)

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A134 Removal Procedure4. Remove the right side panel.1Remove the 2 screws on the rear side.2Release the out

Pagina 52 - 3.8 Outdoor Fan Control

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1354Remove the 4 screws on the right side panel.5Remove the screw near the stop valves.S

Pagina 53 - 3.10 Defrost Control

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A136 Removal Procedure6Unfasten the hook on the rear side.When reassembling, make sure to fit the hook.7Li

Pagina 54 - 44 Function and Control

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1372.2 Removal of Electrical BoxProcedure Warning Be sure to wait 10 minutes or more aft

Pagina 55 - Minimum opening (pulse) 52

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A138 Removal Procedure4Disconnect the connector for the overload protector [S40].5Disconnect the connector

Pagina 56 - (seconds) 810

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1397Release the discharge pipe thermistor.Be careful not to lose the clip for the therm

Pagina 57 - 3.12 Malfunctions

SiBE05-722_ASpecifications 5Part 2Specifications1. Specifications ...

Pagina 58 - 3.13 Forced Operation Mode

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A140 Removal Procedure10Lift and remove the electrical box.StepProcedure Points(R7223)Electrical Box

Pagina 59 - Operation Manual

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1412.3 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning

Pagina 60 - 1. System Configuration

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A142 Removal Procedure4Remove the 4 screws.56Unfasten the 3 hooks on the upper side.Lift and pull out the m

Pagina 61 - 2. Operation Manual

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1432.4 Removal of Reactor / Partition PlateProcedure Warning Be sure to wait 10 minutes

Pagina 62 -  To stop operation

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A144 Removal Procedure2The partition plate has a hook on the lower side. Lift and pull the partition plate

Pagina 63 - Operation Manual 53

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1452.5 Removal of Sound BlanketProcedure Warning Be sure to wait 10 minutes or more afte

Pagina 64 - To adjust the horizontal

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A146 Removal Procedure4Pull the sound blanket (inner) out.5Pull the sound blanket (bottom) out.StepProcedur

Pagina 65 - (louvers)

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1472.6 Removal of Four Way ValveProcedure Warning Be sure to wait for 10 minutes or more

Pagina 66 - To cancel POWERFUL

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A148 Removal Procedure4Remove the screw and remove the four way valve coil.WarningBe careful not to get you

Pagina 67 - OUTDOOR UNIT QUIET Operation

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 149Note:Do not use a metal saw for cutting pipes by all means because the sawdust comes

Pagina 68 - HOME LEAVE Operation

Specifications SiBE05-722_A6 Specifications1. Specifications1.1 Cooling Only50 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown

Pagina 69 - 2.Use as a favorite mode

Outdoor Unit - RK(X)S25/35E2V1B SiBE05-722_A150 Removal Procedure2.7 Removal of CompressorProcedure Warning Be sure to wait for 10 minutes or more aft

Pagina 70 - To use OFF TIMER opera

SiBE05-722_A Outdoor Unit - RK(X)S25/35E2V1BRemoval Procedure 1513Heat up the brazed part of the suction side and disconnect.Note:Do not use a metal

Pagina 71 -  To use ON TIMER operation

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A152 Removal Procedure3. Outdoor Unit - RK(X)S25/35G2V1B3.1 Removal of Outer Panels / Fan MotorProcedure Wa

Pagina 72 - Service Diagnosis

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1532Remove the 2 screws and lift the top panel.3Remove the drip proof plate.4Remove the

Pagina 73 - 1. Caution for Diagnosis

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A154 Removal Procedure5Remove the 8 screws of the front panel.6Unfasten the hooks.Pull and remove the front

Pagina 74

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1553. Remove the fan motor.The screw has reverse winding.Nut size: M61Remove the washe

Pagina 75 - < ARC433 Series >

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A156 Removal Procedure4Disconnect the connector for the fan motor [S70].5Release the fan motor lead wire fr

Pagina 76 - 66 Service Diagnosis

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1578Remove the screw and remove the fan motor fixing frame.When reassembling, fit the l

Pagina 77 - Service Diagnosis 67

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A158 Removal Procedure4. Remove the right side panel.1Remove the 2 screws on the rear side.2Release the out

Pagina 78 - 3. Troubleshooting

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1594Remove the 4 screws on the right side panel.5Remove the screw near the stop valves.S

Pagina 79 - (R11704)

SiBE05-722_A SpecificationsSpecifications 750 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table below.ModelIndoor Un

Pagina 80 - 70 Service Diagnosis

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A160 Removal Procedure6Unfasten the hook on the rear side.When reassembling, make sure to fit the hook.7Li

Pagina 81

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1613.2 Removal of Electrical BoxProcedure Warning Be sure to wait for 10 minutes or more

Pagina 82 - 72 Service Diagnosis

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A162 Removal Procedure4Disconnect the connectors for the magnetic relay [S50] and for the thermistors [S90]

Pagina 83 - Service Diagnosis 73

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1637Disconnect the connectors for the filter PCB [HL3] [HN3].8Remove the wire harness fo

Pagina 84 - Outdoor Unit)

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A164 Removal Procedure10Lift and remove the electrical box.StepProcedure Points(R9348)Electrical box

Pagina 85 - Service Diagnosis 75

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1653.3 Removal of ThermistorsProcedure Warning Be sure to wait 10 minutes or more after

Pagina 86 - 76 Service Diagnosis

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A166 Removal Procedure4Feature of the thermistorsStepProcedure Points(R9356)

Pagina 87 - Service Diagnosis 77

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1673.4 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning

Pagina 88 - 3.10 Compressor Lock

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A168 Removal Procedure4Remove the 4 screws.5Unfasten the 3 hooks on the upper side.6Lift and pull out the m

Pagina 89 - 3.11 DC Fan Lock

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1697Feature of the main PCBRefer to page 18 for detail.[S10] [HL3] [HN3]: filter PCB[S2

Pagina 90 - 80 Service Diagnosis

Specifications SiBE05-722_A8 Specifications50 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table below.ModelIndoor Un

Pagina 91 - Service Diagnosis 81

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A170 Removal Procedure3.5 Removal of Reactor / Partition PlateProcedure Warning Be sure to wait 10 minutes

Pagina 92 - 82 Service Diagnosis

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1712The partition plate has a hook on the lower side. Lift and pull the partition plate

Pagina 93

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A172 Removal Procedure3.6 Removal of Sound BlanketProcedure Warning Be sure to wait for 10 minutes or more

Pagina 94 - (R11897)

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1733.7 Removal of Four Way ValveProcedure Warning Be sure to wait for 10 minutes or more

Pagina 95 - Service Diagnosis 85

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A174 Removal Procedure4Remove the screw and remove the four way valve coil.WarningBe careful not to get you

Pagina 96 - 86 Service Diagnosis

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 175Note:Do not use a metal saw for cutting pipes by all means because the sawdust comes

Pagina 97 - Refer to P.110

Outdoor Unit - RK(X)S25/35G2V1B SiBE05-722_A176 Removal Procedure3.8 Removal of CompressorProcedure Warning Be sure to wait for 10 minutes or more aft

Pagina 98 - 88 Service Diagnosis

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1BRemoval Procedure 1773Heat up the brazed part of the suction side and disconnect.Note:Do not use a metal

Pagina 99 - Service Diagnosis 89

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A178 Removal Procedure4. Outdoor Unit - RK(X)S25/35G2V1B94.1 Removal of Outer Panels / Fan MotorProcedure

Pagina 100 - (R11926)

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1792Remove the 2 screws and lift the top panel.3Remove the drip proof plate.4Remove the

Pagina 101 - RK(X)S25/35G2V1B9 98 75 83

SiBE05-722_A SpecificationsSpecifications 91.2 Heat Pump50 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table below.M

Pagina 102 - (R10727)

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A180 Removal Procedure5Remove the 8 screws of the front panel.6Unfasten the hooks.Pull and remove the fron

Pagina 103 - Check No.07

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1813. Remove the fan motor.The screw has reverse winding.Nut size: M61Remove the wash

Pagina 104 - RK(X)S25/35G2V1B9 98 78

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A182 Removal Procedure4Cut the clamp.5Disconnect the connector for the fan motor [S70].6Release the fan mo

Pagina 105 - (R10728)

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1837Remove the screw and remove the fan motor fixing frame.When reassembling, fit the

Pagina 106 - (R12001)

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A184 Removal Procedure8Open the hooks and release the fan motor lead wire.When reassembling, put the fan

Pagina 107 - Service Diagnosis 97

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1852Remove the 4 screws on the right side panel.3Remove the screw near the stop valves.

Pagina 108 - 98 Service Diagnosis

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A186 Removal Procedure5Lift up the right side panel and remove it.When reassembling, make sure to fit the

Pagina 109 - 3.23 Refrigerant Shortage

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1874.2 Removal of Electrical BoxProcedure Warning Be sure to wait 10 minutes or more af

Pagina 110 - Refer to P.105

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A188 Removal Procedure4Disconnect the relay connector for the compressor.5Disconnect the connector for the

Pagina 111 - Service Diagnosis 101

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1898Release the discharge pipe thermistor.Be careful not to lose the clip for the ther

Pagina 112

SiBE05-722_Ai Table of ContentsInverter PairFloor / Ceiling SuspendedDual TypeBA-SerieszCooling OnlyIndoor UnitFLKS25BAVMBFLKS35BAVMBOutdoor UnitRKS25

Pagina 113 - 4. Check

Specifications SiBE05-722_A10 Specifications50 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table below.ModelIndoor U

Pagina 114 - Check No.05

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A190 Removal Procedure4.3 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning

Pagina 115 - (R11905)

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1914Pull out the forced operation button PCB.Disconnect the connector [S110] to remove

Pagina 116 - Check No.08

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A192 Removal Procedure7Release the harness.8Cut the clamps at the 2 locations.9Disconnect the connector fo

Pagina 117 - Service Diagnosis 107

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 19310Disconnect the connectors for the magnetic relay [S50] and for the forced operatio

Pagina 118 - 4.1.9 Power Module Check

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A194 Removal Procedure14Remove the 6 screws.15Unfasten the 4 hooks and remove the main PCB.Refer to page

Pagina 119 - Service Diagnosis 109

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1952. Remove the filter PCB.1Release the harnesses from the hook.2Cut the clamp.3Releas

Pagina 120 - 4.1.11 Hall IC Check

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A196 Removal Procedure4Release the harnesses from the hooks.5Remove the screw.6Unfasten the 2 hooks.7Lift

Pagina 121 - (R12035)

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1978Feature of the filter PCBRefer to page 20 for detail.StepProcedure Points(R11878)

Pagina 122 - Removal Procedure

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A198 Removal Procedure4.4 Removal of Reactor / Partition PlateProcedure Warning Be sure to wait 10 minutes

Pagina 123 - 1. Indoor Unit

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 1992The partition plate has a hook on the lower side. Lift and pull the partition plate

Pagina 124 - Grille fixture

SiBE05-722_A SpecificationsSpecifications 1150 Hz, 220 - 230 - 240 VNote: The data are based on the conditions shown in the table below.ModelIndoor U

Pagina 125 - Side cover

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A200 Removal Procedure4.5 Removal of Sound BlanketProcedure Warning Be sure to wait 10 minutes or more aft

Pagina 126 - 1.2 Removal of Front Panel

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 2014Pull the sound blanket (inner) out.5Pull the sound blanket (bottom) out.StepProcedu

Pagina 127 - Removal Procedure 117

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A202 Removal Procedure4.6 Removal of Four Way ValveProcedure Warning Be sure to wait 10 minutes or more af

Pagina 128 - Horizontal blade

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 2034Remove the screw and remove the four way valve coil.WarningBe careful not to get yo

Pagina 129 - Swing motor

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A204 Removal ProcedureNote:Do not use a metal saw for cutting pipes by all means because the sawdust come

Pagina 130 - Discharge grille

SiBE05-722_A Outdoor Unit - RK(X)S25/35G2V1B9Removal Procedure 2054.7 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after

Pagina 131 - 1.6 Removal of Drain Pan

Outdoor Unit - RK(X)S25/35G2V1B9 SiBE05-722_A206 Removal Procedure3Heat up the brazed part of the suction side and disconnect.Note: Do not use a meta

Pagina 132 - 122 Removal Procedure

SiBE05-722_ATrial Operation and Field Settings 207Part 8Trial Operation andField Settings1. Trial Operation ...

Pagina 133 - Removal Procedure 123

Trial Operation SiBE05-722_A208 Trial Operation and Field Settings1. Trial OperationOutline 1. Measure the supply voltage and make sure that it falls

Pagina 134 - 124 Removal Procedure

SiBE05-722_A Field SettingsTrial Operation and Field Settings 2092. Field Settings2.1 When 2 Units are Installed in 1 RoomWhen 2 indoor units are inst

Pagina 135 - Removal Procedure 125

SiBE05-722_A12 Printed Circuit Board Connector Wiring DiagramPart 3Printed Circuit BoardConnector Wiring Diagram1. Printed Circuit Board Connector Wir

Pagina 136 - Fan motor fixture

Field Settings SiBE05-722_A210 Trial Operation and Field Settings2.2 Standby Electricity SavingOutline RK(X)S25/35G2V1B, RK(X)S25/35G2V1B9 Models Only

Pagina 137 - Piping fixture

SiBE05-722_A Field SettingsTrial Operation and Field Settings 2112.3 Facility Setting Jumper (cooling at low outdoor temperature)Outline For Cooling O

Pagina 138 - Move to right

Field Settings SiBE05-722_A212 Trial Operation and Field SettingsA humidifier might cause dew jumping from the indoor unit outlet vent.4. Cutting jump

Pagina 139 - (R11890)

SiBE05-722_A Application of Silicon Grease to a Power Transistor and a Diode BridgeTrial Operation and Field Settings 2133. Application of Silicon Gre

Pagina 140 - Drip proof plate

SiBE05-722_A214 AppendixPart 9Appendix1. Piping Diagrams...2151.1 Indoo

Pagina 141 - Outdoor fan

SiBE05-722_A Piping DiagramsAppendix 2151. Piping Diagrams1.1 Indoor Unit FLKS25/35BAVMB FLXS25/35BAVMBFIELD PIPINGFIELD PIPING(9. 5CuT)(6. 4CuT)REFRI

Pagina 142 - Bell mouth

Piping Diagrams SiBE05-722_A216 Appendix1.2 Outdoor Unit1.2.1 Cooling OnlyRKS25/35E2V1BRKS25/35G2V1B, RKS25/35G2V1B9M9.5CuTMUFFLER9.5CuTFIELD PIPINGFI

Pagina 143 - Fan motor fixing frame

SiBE05-722_A Piping DiagramsAppendix 2171.2.2 Heat PumpRXS25/35E2V1BRXS25/35G2V1B, RXS25/35G2V1B9M9.5CuTMUFFLERPROPELLER FAN7.9CuT7.9CuTCOMPRESSOR9.5C

Pagina 144 - Guard net

Wiring Diagrams SiBE05-722_A218 Appendix2. Wiring Diagrams2.1 Indoor UnitFLK(X)S25/35BAVMB2.2 Outdoor UnitRK(X)S25/35E2V1BLEDH1PPCB3LEDH2PPCB4S1WLEDH3

Pagina 145 - Right side panel

SiBE05-722_A Wiring DiagramsAppendix 219RK(X)S25/35G2V1BRK(X)S25/35G2V1B9FIELD WIRING.MRM20N=1ORGIPM1FU3X1MDB1indoorL1RZ3CHR120AHR2HL1L1~+BLKORG+1L1MR

Pagina 146 - Procedure Points

SiBE05-722_A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 131. Printed Circuit Board Connector Wiring

Pagina 147 - 2.2 Removal of Electrical Box

WarningDaikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not hav

Pagina 148

Printed Circuit Board Connector Wiring Diagram SiBE05-722_A14 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1) : Control PCBPCB (2) :

Pagina 149 - (R12279)

SiBE05-722_A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 151.2 Outdoor Unit1.2.1 RK(X)S25/35E2V1BConn

Pagina 150 - Electrical Box

Printed Circuit Board Connector Wiring Diagram SiBE05-722_A16 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Filter PCBPCB (2): Mai

Pagina 151 - 2.3 Removal of PCB

SiBE05-722_A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 171.2.2 RK(X)S25/35G2V1BConnectors and Other

Pagina 152 - [S90][S30]

Printed Circuit Board Connector Wiring Diagram SiBE05-722_A18 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Filter PCBPCB (2): Mai

Pagina 153 - Partition plate

SiBE05-722_A Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 191.2.3 RK(X)S25/35G2V1B9Connectors and Othe

Pagina 154 - 144 Removal Procedure

SiBE05-722_ATable of Contents ii1. Introduction ...v1.1 Safe

Pagina 155 - 2.5 Removal of Sound Blanket

Printed Circuit Board Connector Wiring Diagram SiBE05-722_A20 Printed Circuit Board Connector Wiring DiagramPCB Detail PCB (1): Filter PCBPCB (2): Mai

Pagina 156 - (R11888)

SiBE05-722_AFunction and Control 21Part 4Function and Control1. Main Functions...

Pagina 157 - 2.6 Removal of Four Way Valve

Main Functions SiBE05-722_A22 Function and Control1. Main Functions1.1 Temperature ControlDefinitions of TemperaturesThe definitions of temperatures a

Pagina 158 - Four way valve

SiBE05-722_A Main FunctionsFunction and Control 23Drawing of InverterThe following drawing shows a schematic view of the inverter principle:Inverter F

Pagina 159 - Removal Procedure 149

Main Functions SiBE05-722_A24 Function and Control1.3 Airflow Direction ControlAuto-Swing The following table explains the auto-swing process for cool

Pagina 160 - 2.7 Removal of Compressor

SiBE05-722_A Main FunctionsFunction and Control 251.4 Fan Speed Control for Indoor UnitsOutline Phase control and fan speed control contains 9 steps:

Pagina 161 - Suction side

Main Functions SiBE05-722_A26 Function and Control1.5 Program Dry OperationOutline Program dry operation removes humidity while preventing the room te

Pagina 162 - Shield plate

SiBE05-722_A Main FunctionsFunction and Control 271.6 Automatic OperationOutline Automatic Cooling / Heating FunctionWhen the AUTO mode is selected wi

Pagina 163 - INVERTER

Main Functions SiBE05-722_A28 Function and Control1.7 Thermostat ControlThermostat control is based on the difference between the room thermistor temp

Pagina 164

SiBE05-722_A Main FunctionsFunction and Control 291.8 NIGHT SET ModeOutline When the OFF timer is set, the NIGHT SET Mode is automatically activated.

Pagina 165

SiBE05-722_Aiii Table of ContentsPart 5 Operation Manual ... 491. System Configuration...

Pagina 166 - Lead wire Outdoor fan

Main Functions SiBE05-722_A30 Function and Control1.9 HOME LEAVE OperationOutline HOME LEAVE operation is a function that allows you to record your fa

Pagina 167

SiBE05-722_A Main FunctionsFunction and Control 311.10 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full

Pagina 168

Main Functions SiBE05-722_A32 Function and Control1.11 Other Functions1.11.1 Hot-Start FunctionIn order to prevent the cold air blast that normally co

Pagina 169

SiBE05-722_A Function of ThermistorFunction and Control 332. Function of ThermistorCooling OnlyHeat PumpA Outdoor Heat Exchanger Thermistor 1. The o

Pagina 170 - 160 Removal Procedure

Control Specification SiBE05-722_A34 Function and Control3. Control Specification3.1 Mode HierarchyOutline There are two modes; the one is the normal

Pagina 171 - 3.2 Removal of Electrical Box

SiBE05-722_A Control SpecificationFunction and Control 353.2 Frequency ControlOutline Frequency is determined according to the difference between the

Pagina 172

Control Specification SiBE05-722_A36 Function and Control2. Determine upper limit frequencyThe minimum value is set as an upper limit frequency among

Pagina 173 - Wire harness

SiBE05-722_A Control SpecificationFunction and Control 373.3 Controls at Mode Changing / Start-up3.3.1 Preheating OperationOutline The inverter operat

Pagina 174 - Lift and remove the

Control Specification SiBE05-722_A38 Function and Control3.3.2 Four Way Valve SwitchingOutline In heating operation, current is conducted, and in coo

Pagina 175 - 3.3 Removal of Thermistors

SiBE05-722_A Control SpecificationFunction and Control 393.4 Discharge Pipe Temperature ControlOutline The discharge pipe temperature is used as the i

Pagina 176 - Feature of the

SiBE05-722_ATable of Contents iv1.5 Removal of Discharge Grille...1201.6 Removal of Drai

Pagina 177 - 3.4 Removal of PCB

Control Specification SiBE05-722_A40 Function and Control3.5 Input Current ControlOutline The microcomputer calculates the input current during the co

Pagina 178 - Lift and pull out the

SiBE05-722_A Control SpecificationFunction and Control 413.6 Freeze-up Protection ControlOutline During cooling operation, the signal sent from the in

Pagina 179 - [S20][S80][HL3][HN3]

Control Specification SiBE05-722_A42 Function and Control3.8 Outdoor Fan Control1. Fan OFF delay when stoppedThe outdoor fan is turned OFF 60 seconds

Pagina 180

SiBE05-722_A Control SpecificationFunction and Control 433.10 Defrost ControlOutline Defrosting is carried out by the cooling cycle (reverse cycle). T

Pagina 181 - Removal Procedure 171

Control Specification SiBE05-722_A44 Function and Control3.11 Electronic Expansion Valve ControlOutline The following items are included in the electr

Pagina 182 - 3.6 Removal of Sound Blanket

SiBE05-722_A Control SpecificationFunction and Control 453.11.1 Fully Closing with Power ONThe electronic expansion valve is initialized when turning

Pagina 183 - 3.7 Removal of Four Way Valve

Control Specification SiBE05-722_A46 Function and ControlDetail When the starting control (cooling : seconds, heating : seconds) finishes, the det

Pagina 184

SiBE05-722_A Control SpecificationFunction and Control 473.12 Malfunctions3.12.1 Sensor Malfunction DetectionSensor malfunction may occur in the therm

Pagina 185 - Removal Procedure 175

Control Specification SiBE05-722_A48 Function and Control3.13 Forced Operation ModeOutline Forced operation mode includes only forced cooling.Detail3.

Pagina 186 - 3.8 Removal of Compressor

SiBE05-722_AOperation Manual 49Part 5Operation Manual1. System Configuration...

Pagina 187

Introduction SiBE05-722_Av1. Introduction1.1 Safety CautionsCautions and WarningsBe sure to read the following safety cautions before conducting repa

Pagina 188

System Configuration SiBE05-722_A50 Operation Manual1. System ConfigurationAfter the installation and test operation of the room air conditioner have

Pagina 189

SiBE05-722_A Operation ManualOperation Manual 512. Operation Manual2.1 Remote Controller6 Remote Controller1. Signal transmitter:•It sends signals to

Pagina 190

Operation Manual SiBE05-722_A52 Operation Manual2.2 AUTO · DRY · COOL · HEAT · FAN Operation10AUTO · DRY · COOL · HEAT · FAN Operation To start opera

Pagina 191 - (R11827)

SiBE05-722_A Operation ManualOperation Manual 5311 To change the air flow rate setting5. Press “FAN setting button”.• Indoor unit quiet operationWhen

Pagina 192

Operation Manual SiBE05-722_A54 Operation Manual2.3 Adjusting the Airflow Direction12Adjusting the Air Flow Direction1. Press “SWING button”.•2.• The

Pagina 193 - (R12314)

SiBE05-722_A Operation ManualOperation Manual 5513•Hold the knob and move the louvers. (You will find a knob on the left side and the right side blad

Pagina 194 - (R12162)

Operation Manual SiBE05-722_A56 Operation Manual2.4 POWERFUL Operation14POWERFUL Operation1. Press “POWERFUL button”.••• “ ” is displayed on the

Pagina 195 - (R11842)

SiBE05-722_A Operation ManualOperation Manual 572.5 OUTDOOR UNIT QUIET Operation15OUTDOOR UNIT QUIET Operation1. Press “QUIET button”.• “ ” is d

Pagina 196 - (R11841)

Operation Manual SiBE05-722_A58 Operation Manual2.6 HOME LEAVE Operation16HOME LEAVE Operation1. Press “HOME LEAVE button” .• The HOME LEAVE lamp lig

Pagina 197 - 4.2 Removal of Electrical Box

SiBE05-722_A Operation ManualOperation Manual 5917 What’s the HOME LEAVE operation? Useful in these cases1.Use as an energy-saving mode.• Every day

Pagina 198 - (R11851)

SiBE05-722_A IntroductionviBe sure to wear a safety helmet, gloves, and a safety belt when working at a high place (more than 2 m). Insufficient safet

Pagina 199 - Removal Procedure 189

Operation Manual SiBE05-722_A60 Operation Manual2.7 TIMER Operation18TIMER Operation• Check that the clock is correct.If not, set the clock to the pr

Pagina 200 - 4.3 Removal of PCB

SiBE05-722_A Operation ManualOperation Manual 6119 To use ON TIMER operation•1. Press “ON TIMER button”.is displayed.blinks.2.•3.•The TIMER lamp ligh

Pagina 201 - (R11858)

SiBE05-722_A62 Service DiagnosisPart 6Service Diagnosis1. Caution for Diagnosis...

Pagina 202 - (R11861)

SiBE05-722_A Caution for DiagnosisService Diagnosis 631. Caution for Diagnosis1.1 Troubleshooting with LEDIndoor Unit The operation lamp blinks when a

Pagina 203 - (R11862)

Problem Symptoms and Measures SiBE05-722_A64 Service Diagnosis2. Problem Symptoms and MeasuresSymptom Check Item Details of Measure ReferencePageThe u

Pagina 204 - 194 Removal Procedure

SiBE05-722_A Problem Symptoms and MeasuresService Diagnosis 652.1 ARC433 SeriesCheck Method 1 1. When the timer cancel button is held down for 5 secon

Pagina 205 - (R11872)

Problem Symptoms and Measures SiBE05-722_A66 Service DiagnosisCheck Method 21. Press the center of the TEMP button and the MODE button at the same tim

Pagina 206 - (R11877)

SiBE05-722_A Problem Symptoms and MeasuresService Diagnosis 675. Press the TEMP▲ or ▼ button and change the figure until you hear the sound of “beep”.

Pagina 207 - (R11878)

Troubleshooting SiBE05-722_A68 Service Diagnosis3. Troubleshooting3.1 Error Codes and Description★: Displayed only when system-down occurs.Error Codes

Pagina 208 - (R12273)

SiBE05-722_A TroubleshootingService Diagnosis 693.2 Indoor Unit PCB AbnormalityRemote Controller DisplayA1Method of Malfunction DetectionEvaluation of

Pagina 209 - (R11883)

Introduction SiBE05-722_Avii1.1.2 Cautions Regarding Safety of UsersWarningBe sure to use parts listed in the service parts list of the applicable mod

Pagina 210 - (R11885)

Troubleshooting SiBE05-722_A70 Service Diagnosis3.3 Freeze-up Protection Control or Heating Peak-cut ControlRemote Controller DisplayA5Method of Malfu

Pagina 211

SiBE05-722_A TroubleshootingService Diagnosis 71TroubleshootingCheck No.06Refer to P.105NONONOCheck No. 06Check the indoor heat exchanger thermistor.Y

Pagina 212 - 4.6 Removal of Four Way Valve

Troubleshooting SiBE05-722_A72 Service Diagnosis3.4 Fan Motor (AC Motor) or Related AbnormalityRemote Controller DisplayA6Method of Malfunction Detect

Pagina 213

SiBE05-722_A TroubleshootingService Diagnosis 733.5 Thermistor or Related Abnormality (Indoor Unit)Remote Controller DisplayC4, C9 Method of Malfunct

Pagina 214 - 204 Removal Procedure

Troubleshooting SiBE05-722_A74 Service Diagnosis3.6 Signal Transmission Error (between Indoor Unit and Outdoor Unit)Remote Controller DisplayU4Method

Pagina 215 - 4.7 Removal of Compressor

SiBE05-722_A TroubleshootingService Diagnosis 753.7 Unspecified Voltage (between Indoor Unit and Outdoor Unit)Remote Controller Display UAMethod of Ma

Pagina 216

Troubleshooting SiBE05-722_A76 Service Diagnosis3.8 Outdoor Unit PCB AbnormalityRemote Controller Display E1Method of Malfunction DetectionThe system

Pagina 217 - Field Settings

SiBE05-722_A TroubleshootingService Diagnosis 773.9 OL Activation (Compressor Overload)Remote Controller DisplayE5Method of Malfunction DetectionA com

Pagina 218 - (2) (3) (4)

Troubleshooting SiBE05-722_A78 Service Diagnosis3.10 Compressor LockRemote Controller DisplayE6Method of Malfunction DetectionA compressor lock is det

Pagina 219 - 2. Field Settings

SiBE05-722_A TroubleshootingService Diagnosis 793.11 DC Fan LockRemote Controller DisplayE7Method of Malfunction DetectionAn error is determined with

Pagina 220 - Function OFF Function ON

SiBE05-722_A IntroductionviiiCheck to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet securely.If

Pagina 221 - Cut the jumper J4

Troubleshooting SiBE05-722_A80 Service Diagnosis3.12 Input Overcurrent DetectionRemote Controller DisplayE8Method of Malfunction DetectionAn input ove

Pagina 222

SiBE05-722_A TroubleshootingService Diagnosis 813.13 Four Way Valve AbnormalityRemote Controller DisplayEAMethod of Malfunction DetectionThe room temp

Pagina 223 - Transistor and a Diode Bridge

Troubleshooting SiBE05-722_A82 Service DiagnosisTroubleshootingCheck No.05Refer to P.104Check No.06Refer to P.105Check No.11Refer to P.107NGOKNOOKNGOK

Pagina 224 - Appendix

SiBE05-722_A TroubleshootingService Diagnosis 833.14 Discharge Pipe Temperature ControlRemote Controller DisplayF3Method of Malfunction DetectionAn er

Pagina 225 - 1. Piping Diagrams

Troubleshooting SiBE05-722_A84 Service Diagnosis3.15 High Pressure Control in CoolingRemote Controller DisplayF6Method of Malfunction DetectionHigh-pr

Pagina 226 - 1.2 Outdoor Unit

SiBE05-722_A TroubleshootingService Diagnosis 853.16 Compressor System Sensor AbnormalityRemote Controller Display H0Method of Malfunction DetectionT

Pagina 227 - 1.2.2 Heat Pump

Troubleshooting SiBE05-722_A86 Service Diagnosis3.17 Position Sensor AbnormalityRemote Controller DisplayH6Method of Malfunction DetectionA compressor

Pagina 228 - 2. Wiring Diagrams

SiBE05-722_A TroubleshootingService Diagnosis 87TroubleshootingCheck No.29Refer to P.110CautionBe sure to turn off the power switch before connecting

Pagina 229 - 3D065704A

Troubleshooting SiBE05-722_A88 Service Diagnosis3.18 DC Voltage / Current Sensor AbnormalityRemote Controller DisplayH8Method of Malfunction Detection

Pagina 230 - Cautions on product corrosion

SiBE05-722_A TroubleshootingService Diagnosis 893.19 Thermistor or Related Abnormality (Outdoor Unit)Remote Controller Display H9, J3, J6, P4Method of