MODELS
(Ceiling mounted Multi flow cassette type)
FCQ71DV3B FCQ71DAV3B
FCQ100DV3B FCQ100DAV3B
FCQ125DV3B FCQ125DAV3B
FCQ140DV3B FCQ140DAV3B
SPLIT SYSTEM Air Conditioners
INSTALLATION MANUAL
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION.
KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
LESEN SIE DIESE ANWEISUNGEN VOR DER INSTALLATION SORGFÄLTIG DURCH.
BEWAHREN SIE DIESE ANLEITUNG FÜR SPÄTERE BEZUGNAHME GRIFFBEREIT
AUF.
LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L’INSTALLATION.
CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE.
LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR.
GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER
ALGUNA DUDA.
PRIMA DELL’INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI.
TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI.
ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ
ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ.
LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE. BEWAAR DEZE
HANDLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG.
LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE REALIZAR A INSTALAÇÃO.
MANTENHA ESTE MANUAL AO SEU ALCANCE PARA FUTURAS CONSULTAS.
ПЕРЕД НАЧАЛОМ МОНТАЖА ВНИМАТЕЛЬНО ОЗНАКОМЬТЕСЬ С ДАННЫМИ
ИНСТРУКЦИЯМИ. СОХРАНИТЕ ДАННОЕ РУКОВОДСТВО В МЕСТЕ, УДОБНОМ ДЛЯ
ОБРАЩЕНИЯ В БУДУЩЕМ.
English
Deutsch
Français
Español
Italiano
ΕλληνικÜ
Nederlands
Portugues
Рóссêий
00_CV_3P184443-6.fm Page 1 Monday, July 3, 2006 9:02 AM
Vedere la pagina 0
1 2 3 4 5 6 ... 27 28

Sommario

Pagina 1 - INSTALLATION MANUAL

MODELS(Ceiling mounted Multi flow cassette type)FCQ71DV3B FCQ71DAV3BFCQ100DV3B FCQ100DAV3BFCQ125DV3B FCQ125DAV3BFCQ140DV3B FCQ140DAV3BSPLIT SYSTEM Air

Pagina 2 - 3P154437-1A

8 English5. INDOOR UNIT INSTALLATIONInstalling optional accessories (except for the decoration panel) before installing the indoor unit is easier. How

Pagina 3 - 1. SAFETY CONSIDERATIONS

English 9<Ceiling work>(1-3) Adjust the unit to the right position for installation.(Refer to “4. PREPARATIONS BEFORE INSTALLATION-(1)”.)(1-4) C

Pagina 4

10 English• The outdoor unit is charged with refrigerant.• Be sure to use both a spanner and torque wrench together, as shown in the drawing, when con

Pagina 5 - 2. BEFORE INSTALLATION

English 11• Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas leakage by thoroughly studying the

Pagina 6 - 3. OPTIONAL ACCESSORIES

12 English7. DRAIN PIPING WORK(1) Rig drain piping• As for drain work, perform piping in such a manner that water can be drained properly.As for drain

Pagina 7 - 4. NOTE TO THE INSTALLER

English 13<PRECAUTIONS FOR DRAIN RAISING PIPING>• Install the drain raising pipes at a height of less than 550 mm.• Install the drain raising pi

Pagina 8

14 EnglishCAUTIONDrain piping connectionsDo not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew-age mi

Pagina 9

English 158. ELECTRIC WIRING WORK• All field supplied parts and materials and electric works must conform to local codes.• Use copper wire only.• For

Pagina 10 - 5. INDOOR UNIT INSTALLATION

16 EnglishObserve the notes mentioned below when wiring to the terminal block for wiring the units.CAUTION• When clamping wiring, use the included cla

Pagina 11 - 6. REFRIGERANT PIPING WORK

English 17• Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may cause overheating.) (Refer to

Pagina 12 - 90˚±0.5˚

Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,Kita-ku, Osaka, 530-8323 JapanDAIKIN INDUSTRIES, LTD.EN60335-2-40,FCQ71DV3B, FCQ100DV3B, FCQ125DV3B,

Pagina 13 - Nitrogen

18 EnglishNOTE1.All transmission wiring except for the remote controller wires is polarized and must match the terminal symbol.2. In case a shielding

Pagina 14 - 7. DRAIN PIPING WORK

English 1910. FIELD SETTINGMake sure the terminal box lids are closed on the indoor and outdoor units.Field setting must be made from the remote contr

Pagina 15

20 EnglishWhen using wireless remote controllers• When using wireless remote controllers, wireless remote controller address setting is necessary. Ref

Pagina 16 - (50Hz 230V, 240V)

English 2110-7 Control by 2 Remote Controllers (Controlling 1 indoor unit by 2 remote controllers)• When using 2 remote controllers, one must be set t

Pagina 17 - 8. ELECTRIC WIRING WORK

22 EnglishPRECAUTIONS1. Refer to the diagnoses below if the unit does not operate properly.2. After completing the test run, press the INSPECTION/TEST

Pagina 18 - P1 P2 F1 F2

English 2312-3 Malfunction code list• For plases where the Malfunction code is left blank, the “ ” indication is not displayed. Though the system cont

Pagina 19 - 9. WIRING EXAMPLE

24 EnglishL9Stall prevention (outdoor unit)Compressor possibly locked.LC Transmission malfunction between the outdoor control units’ inverters (outdoo

Pagina 20 - 1 P2 P1 P2

English 2513. WIRING DIAGRAMREMOTE CONTROLLERIN CASE OF SIMULTANEOUS OPERATION SYSTEMINDOOR UNIT (MASTER)INDOOR UNIT (SLAVE)RECEIVER/DISPLAY UNITNOTE)

Pagina 21 - 10. FIELD SETTING

(0608) HT3P184443-6 EM04A037B00_CV_3P184443-6.fm Page 2 Monday, July 3, 2006 9:02 AM

Pagina 22 - Indoor unit 3

English 1FCQ71DV3B FCQ71DAV3BFCQ100DV3B FCQ100DAV3BFCQ125DV3B FCQ125DAV3BFCQ140DV3B FCQ140DAV3BSPLIT SYSTEM Air Conditioners Installation manualCONTEN

Pagina 23 - 12. TEST OPERATION

2 English• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel

Pagina 24 - 12-2 Cautions for servicing

English 32. BEFORE INSTALLATIONDo not exert pressure on the resin parts when opening the unit or when moving it after openingBe sure to check the type

Pagina 25 - 12-3 Malfunction code list

4 English3. OPTIONAL ACCESSORIES• The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2)(However

Pagina 26

English 5Points for explanation about operations4. NOTE TO THE INSTALLERBe sure to instruct customers how to properly operate the unit (especially cle

Pagina 27 - WIRING DIAGRAM

6 EnglishCAUTION• Any vents, light fixtures, or other appliances which may disturb the airflow might cause the top side to become dirty if located too

Pagina 28 - (0608) HT

English 7 Installation is possible when ceiling opening dimensions is as follows• When installing the unit within the frame for fixing false ceiling.