Daikin FTKS20DVMW Specifiche

Navigare online o scaricare Specifiche per Climatizzatori a split Daikin FTKS20DVMW. Daikin FTKS20DVMW Specifications Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 0
SiEBE04-507
Service Manual
/ Inverter Pair Wall Mounted Type D-Series
SiEBE04-507
Inverter Pair
Wall Mounted Type D-Series
Ser vice
Manual
[Applied Models]
zInverter Pair : Cooling Only
zInverter Pair : Heat Pump
Daikin Europe N.V. participates in the Eurovent
Certification Programme for Air Conditioners (AC),
Liquid Chilling Packages (LCP) and Fan Coil Units (FC);
the certified data of certified models are listed in the
Eurovent Directory.
ISO14001 assures an effective environmental
management system in order to help protect human
health and the environment from the potential impact
of our activities, products and services and to assist in
maintaining and improving the quality of the
environment.
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance
regarding design, development, manufacturing as well
as to services related to the product.
Daikin units comply with the European regulations that
guarantee the safety of the product.
Zandvoordestraat 300
B-8400 Ostend - Belgium
www.daikineurope.com
SiEBE04-507 • 06/2005
Prepared in Belgium by Lannoo
Specifications are subject to change without prior notice
Vedere la pagina 0
1 2 3 4 5 6 ... 204 205

Sommario

Pagina 1 - Ser vice

SiEBE04-507Service Manual / Inverter Pair Wall Mounted Type D-SeriesSiEBE04-507Inverter PairWall Mounted Type D-SeriesSer viceManual[Applied Models]zI

Pagina 2

Introduction SiEBE04-507viii1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon i

Pagina 3 - D-Series

Troubleshooting SiEBE04-50790 Service DiagnosisTroubleshootingCheck No.6Refer to P.122NONONOCheck No. 6Indoor unit heat exchangerthermistor checkCheck

Pagina 4

SiEBE04-507 TroubleshootingService Diagnosis 914.4 Fan Motor (DC Motor) or Related AbnormalityRemoteControllerDisplayA6Method of Malfunction Detection

Pagina 5 - Table of Contents iii

Troubleshooting SiEBE04-50792 Service DiagnosisTroubleshootingCheck No.01Refer to P.120Replace fan motor.Replace indoor unit PCB.Replace indoor unit P

Pagina 6

SiEBE04-507 TroubleshootingService Diagnosis 934.5 Thermistor or Related Abnormality (Indoor Unit)RemoteControllerDisplayC4, C9 Method of Malfunction

Pagina 7 - 1. Introduction

Troubleshooting SiEBE04-50794 Service Diagnosis4.6 Signal Transmission Error (between Indoor and Outdoor Unit)RemoteControllerDisplayU4Method of Malfu

Pagina 8

SiEBE04-507 TroubleshootingService Diagnosis 954.7 Unspecified Voltage (between Indoor and Outdoor Units)RemoteControllerDisplayUAMethod of Malfunctio

Pagina 9 - 1.1.3 Inspection after Repair

Troubleshooting SiEBE04-50796 Service Diagnosis4.8 Outdoor Unit PCB AbnormalityRemoteControllerDisplayE1Method of Malfunction Detection The system fo

Pagina 10 - 1.1.5 Using Icons List

SiEBE04-507 TroubleshootingService Diagnosis 974.9 OL Activation (Compressor Overload)RemoteControllerDisplayE5Method of Malfunction DetectionA compre

Pagina 11 - List of Functions

Troubleshooting SiEBE04-50798 Service Diagnosis4.10 Compressor LockRemoteControllerDisplayE6Method of Malfunction DetectionA compressor lock is detect

Pagina 12 - 1. List of Functions

SiEBE04-507 TroubleshootingService Diagnosis 994.11 DC Fan LockRemoteControllerDisplayE7Method of Malfunction DetectionA fan motor or related error is

Pagina 13 - List of Functions 3

SiEBE04-507List of Functions 1Part 1List of Functions1. List of Functions ...

Pagina 14 - 4 List of Functions

Troubleshooting SiEBE04-507100 Service Diagnosis4.12 Input Over Current DetectionRemoteControllerDisplayE8Method of Malfunction DetectionAn input over

Pagina 15 - Specifications

SiEBE04-507 TroubleshootingService Diagnosis 1014.13 Four Way Valve AbnormalityRemoteControllerDisplayEAMethod of Malfunction DetectionThe indoor air

Pagina 16 - 1. Specifications

Troubleshooting SiEBE04-507102 Service DiagnosisTroubleshootingCheck No.5Refer to P.121Check No.6Refer to P.122Check No.11Refer to P.124Correct.Reconn

Pagina 17 - 230V, 50Hz

SiEBE04-507 TroubleshootingService Diagnosis 1034.14 Discharge Pipe Temperature ControlRemoteControllerDisplayF3Method of Malfunction DetectionThe dis

Pagina 18 - 8 Specifications

Troubleshooting SiEBE04-507104 Service Diagnosis4.15 High Pressure Control in CoolingRemoteControllerDisplayF6Method of Malfunction DetectionHigh-pres

Pagina 19 - 1.2 Heat Pump

SiEBE04-507 TroubleshootingService Diagnosis 105TroubleshootingCheck No.4Refer to P.120Check No.6Refer to P.122Check No.7Refer to P.123Check No.9Refer

Pagina 20 - 10 Specifications

Troubleshooting SiEBE04-507106 Service Diagnosis4.16 Compressor System Sensor AbnormalityRemoteControllerDisplayHOMethod of Malfunction Detection The

Pagina 21 - Specifications 11

SiEBE04-507 TroubleshootingService Diagnosis 1074.17 Position Sensor AbnormalityRemoteControllerDisplayH6Method of Malfunction DetectionA compressor s

Pagina 22 - 12 Specifications

Troubleshooting SiEBE04-507108 Service Diagnosis4.18 DC Voltage / Current Sensor AbnormalityRemoteControllerDisplayH8Method of Malfunction DetectionDe

Pagina 23 - Specifications 13

SiEBE04-507 TroubleshootingService Diagnosis 1094.19 Thermistor or Related Abnormality (Outdoor Unit)RemoteControllerDisplayP4, J3, J6, H9Method of Ma

Pagina 24 - 14 Specifications

List of Functions SiEBE04-5072 List of Functions1. List of FunctionsCategory FunctionsFTKS20-35DVMW(L)RKS20-35DVMBFTXS20-35DVMW(L)RXS20-35DVMBCategory

Pagina 25 - Connector Wiring Diagram

Troubleshooting SiEBE04-507110 Service DiagnosisTroubleshootingCheck No.6Refer to P.122P4 : Radiation fin thermistorJ3 : Discharge pipe thermistorJ6 :

Pagina 26 - 1.1 Indoor Unit

SiEBE04-507 TroubleshootingService Diagnosis 1114.20 Electrical Box Temperature RiseRemoteControllerDisplayL3Method of Malfunction DetectionAn electri

Pagina 27 - PCB(1): Control PCB

Troubleshooting SiEBE04-507112 Service DiagnosisTroubleshootingCheck No.6Refer to P.122Check No.7Refer to P.123Check No.9Refer to P.124Turn off the po

Pagina 28 - 1.2 Outdoor Unit

SiEBE04-507 TroubleshootingService Diagnosis 1134.21 Radiation Fin Temperature RiseRemoteControllerDisplayL4Method of Malfunction DetectionA radiation

Pagina 29 - PCB Detail PCB(1): Filter PCB

Troubleshooting SiEBE04-507114 Service DiagnosisTroubleshootingCheck No.6Refer to P.122Check No.7Refer to P.123Check No.9Refer to P.124Turn off the po

Pagina 30

SiEBE04-507 TroubleshootingService Diagnosis 1154.22 Output Over Current DetectionRemoteControllerDisplayL5Method of Malfunction DetectionAn output ov

Pagina 31 - Function and Control

Troubleshooting SiEBE04-507116 Service DiagnosisTroubleshootingCheck No.7Refer to P.123Check No.8Refer to P.123Check No.13Refer to P.125Note: If the m

Pagina 32 - 1. Main Functions

SiEBE04-507 TroubleshootingService Diagnosis 1174.23 Insufficient GasRemoteControllerDisplayU0Method of Malfunction DetectionGas shortage detection I

Pagina 33 - Operation

Troubleshooting SiEBE04-507118 Service DiagnosisTroubleshootingCheck No.4Refer to P.120Check No.6Refer to P.122Reconnect in position.Open the stop val

Pagina 34

SiEBE04-507 TroubleshootingService Diagnosis 1194.24 Over-voltage DetectionRemoteControllerDisplayU2Method of Malfunction DetectionAn abnormal voltage

Pagina 35 - (R4085) (R4085)

SiEBE04-507 List of FunctionsList of Functions 3Category FunctionsFTKS20-35DVMW9RKS20-35DVMBFTXS20-35DVMW9RXS20-35DVMBCategory FunctionsFTKS20-35DVMW9

Pagina 36 - 1.4 Programme Dry Function

Check SiEBE04-507120 Service Diagnosis5. Check5.1 How to Check5.1.1 Fan Motor Connector Output CheckCheck No.01 1. Check connector connection.2. Check

Pagina 37 - 1.5 Automatic Operation

SiEBE04-507 CheckService Diagnosis 1215.1.3 Four Way Valve Performance CheckCheck No.5Turn off the power and turn it on again.Start the heating-mode r

Pagina 38 - 1.6 Thermostat Control

Check SiEBE04-507122 Service Diagnosis5.1.4 Thermistor Resistance CheckCheck No.6 Remove the connectors of the thermistors on the PCB, and measure the

Pagina 39 - 1.7 NIGHT SET Mode

SiEBE04-507 CheckService Diagnosis 1235.1.5 Installation Condition CheckCheck No.75.1.6 Discharge Pressure CheckCheck No.8Installation condition check

Pagina 40 - 1.8 ECONO Mode

Check SiEBE04-507124 Service Diagnosis5.1.7 Outdoor Unit Fan System CheckCheck No.9 DC motor 5.1.8 Power Supply Waveforms CheckCheck No.10 Measure the

Pagina 41 - 1.9 INTELLIGENT EYE

SiEBE04-507 CheckService Diagnosis 1255.1.10 Power Transistor CheckCheck No.13Note: Check to make sure that the voltage between the terminal of Power

Pagina 42 - 32 Function and Control

Check SiEBE04-507126 Service Diagnosis

Pagina 43 - Details of the

SiEBE04-507Removal Procedure 127Part 7Removal Procedure1. Indoor Unit...

Pagina 44 - 1.11 Other Functions

Indoor Unit SiEBE04-507128 Removal Procedure1. Indoor Unit1.1 Removal of Air FilterProcedure Warning Be sure to wait 10 minutes or more after turning

Pagina 45 - 2. Function of Thermistor

SiEBE04-507 Indoor UnitRemoval Procedure 1293. Removing the titanium apatite photocatalytic air-purifying filter1The titanium apatite photocatalytic a

Pagina 46 - 2.2 Cooling Only Model

List of Functions SiEBE04-5074 List of FunctionsCategory FunctionsFTKS20-35D2VMW(L)RKS20-35D2VMB9FTXS20-35D2VMW(L)RXS20-35D2VMB9Category FunctionsFTKS

Pagina 47 - 3. Control Specification

Indoor Unit SiEBE04-507130 Removal Procedure1.2 Removal of Front PanelProcedure Warning Be sure to wait 10 minutes or more after turning off all power

Pagina 48 - 3.2 Frequency Control

SiEBE04-507 Indoor UnitRemoval Procedure 131Step Procedure Points5Remove the front panel. Caution on Mounting When mounting the front panel, fit the

Pagina 49

Indoor Unit SiEBE04-507132 Removal Procedure1.3 Removal of Front GrilleProcedure Warning Be sure to wait 10 minutes or more after turning off all powe

Pagina 50 - 3.3.1 Preheating Operation

SiEBE04-507 Indoor UnitRemoval Procedure 133Step Procedure Points2345Remove the screw covers (one each at the right and left).Remove the screws (one e

Pagina 51 - 3.4 Discharge Pipe Control

Indoor Unit SiEBE04-507134 Removal ProcedureStep Procedure Points67Put your fingers into the front grille and lift the grille up to unfasten the cente

Pagina 52 - 3.5 Input Current Control

SiEBE04-507 Indoor UnitRemoval Procedure 1351.4 Removal of Horizontal Blades and Vertical BladesProcedure Warning Be sure to wait 10 minutes or more a

Pagina 53 - 3.7 Heating Peak-cut Control

Indoor Unit SiEBE04-507136 Removal ProcedureStep Procedure Points2. Removing the horizontal blade (small)123Remove the horizontal blade (small) whileb

Pagina 54 - 3.8 Fan Control

SiEBE04-507 Indoor UnitRemoval Procedure 137Step Procedure Points3. Removing the vertical blade12Unfasten the hooks at the shaft mounting part by pres

Pagina 55 - 3.10 Defrost Control

Indoor Unit SiEBE04-507138 Removal Procedure1.5 Removal of Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Pagina 56 - 46 Function and Control

SiEBE04-507 Indoor UnitRemoval Procedure 139Step Procedure Points5678Remove the drip proof plate by removing the screw.Replace the heatexchanger therm

Pagina 57 - Detail Detect Disconnection

SiEBE04-507Specifications 5Part 2Specifications1. Specifications ...

Pagina 58 - 48 Function and Control

Indoor Unit SiEBE04-507140 Removal ProcedureStep Procedure Points91011Release the hook at the upper far side by pressing it from above and pulling the

Pagina 59 - 3.12 Malfunctions

SiEBE04-507 Indoor UnitRemoval Procedure 1411.6 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning off all power supp

Pagina 60 - 3.14 Additional Function

Indoor Unit SiEBE04-507142 Removal Procedure3. Removing the terminal board1Dismount the terminal board by removing the screw.4. Removing the signal re

Pagina 61 - Function and Control 51

SiEBE04-507 Indoor UnitRemoval Procedure 14334Remove the electrical box by sliding it to the left.Disconnect the wire harness.5. Removing the signal r

Pagina 62 - 52 Function and Control

Indoor Unit SiEBE04-507144 Removal Procedure6. Removing the INTELLIGENT EYE PCB123Remove the INTELLIGENT EYE fixing plate by twisting it clockwise.Rem

Pagina 63 - System Configuration

SiEBE04-507 Indoor UnitRemoval Procedure 145Step Procedure Points7. Removing the display PCB1The figure shows the connection of wire harness for the d

Pagina 64 - 1. System Configuration

Indoor Unit SiEBE04-507146 Removal Procedure2Lift up the bottom of the control PCB and pull it out. When mounting the control PCB, make sure that it

Pagina 65 - 2. Instruction

SiEBE04-507 Indoor UnitRemoval Procedure 1471.7 Removal of Drain Pan UnitProcedure Warning Be sure to turn off all power supplies at least 10 min. bef

Pagina 66 - System relocation

Indoor Unit SiEBE04-507148 Removal Procedure4Remove the drain pan toward yourself from the indoor unit body.Caution on Mounting Make sure that the ho

Pagina 67 - 2.2 Names of parts

SiEBE04-507 Indoor UnitRemoval Procedure 1493. Removing the crank assembly1Remove the screw of the crank assembly.2Remove the crank assembly by unfast

Pagina 68 - Outdoor Unit

Specifications SiEBE04-5076 Specifications1. Specifications1.1 Cooling Only 230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit heigh

Pagina 69 -  Remote Controller

Indoor Unit SiEBE04-507150 Removal Procedure2Remove the drain cap located at the left side of the drain pan unit.3Insert the drain hose to the left si

Pagina 70 - To set the batteries

SiEBE04-507 Indoor UnitRemoval Procedure 1511.8 Removal of Fan MotorProcedure Warning Be sure to turn off all power supplies at least 10 min. before d

Pagina 71 - ATTENTION

Indoor Unit SiEBE04-507152 Removal Procedure4Unfasten the hook (a) of the fan motor fixing plate with your thumb.5Unfasten the hook (c). 6Remove the f

Pagina 72 - Turn the breaker ON

SiEBE04-507 Indoor UnitRemoval Procedure 1531.9 Removal of Heat ExchangerProcedure Warning Be sure to turn off all power supplies at least 10 min. bef

Pagina 73 - 2. Press “ON/OFF button”

Indoor Unit SiEBE04-507154 Removal Procedure2. Removing the indoor unit1Remove the indoor unit from the installation plate.3. Removing the heat exchan

Pagina 74 - 64 System Configuration

SiEBE04-507 Indoor UnitRemoval Procedure 1554After unfastening the lower hooks, hold up the heat exchanger by its left side and lift it up toward your

Pagina 75 - “SWING button” once more

Indoor Unit SiEBE04-507156 Removal Procedure1.10 Removal of Fan RotorProcedure Warning Be sure to turn off all power supplies at least 10 min. before

Pagina 76 - 〈HEAT〉 The flap will go down

SiEBE04-507 Indoor UnitRemoval Procedure 1574Unfasten the hook (a) of the fan motor fixing plate with your thumb and unfasten the hook (b).5The fan mo

Pagina 77 - 2.6 POWERFUL Operation

Indoor Unit SiEBE04-507158 Removal Procedure3. Removing the bearing1Remove the screw of the drip proof plate (left).2The drip proof plate can be remov

Pagina 78 - 1. Press “SILENT button”

SiEBE04-507 Outdoor UnitRemoval Procedure 1592. Outdoor Unit2.1 Removal of Panels and Fan MotorProcedure Warning Be sure to wait 10 minutes or more af

Pagina 79 - 2.8 ECONO Operation

SiEBE04-507 SpecificationsSpecifications 7230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addit

Pagina 80 - 2.9 INTELLIGENT EYE Operation

Outdoor Unit SiEBE04-507160 Removal Procedure2. Remove the panels.1Loosen the 3 screws (front, right, left) and lift the top panel.2Remove the drip pr

Pagina 81 - (Top View)

SiEBE04-507 Outdoor UnitRemoval Procedure 1615Undo the hooks.Pull and remove the front panel. The front panel has 4 hooks. The fan motor is united w

Pagina 82 - 2.10 TIMER Operation

Outdoor Unit SiEBE04-507162 Removal Procedure3Loosen the 2 screws and lift the bell mouth to undo the hooks.Remove the bell mouth.4Loosen the fixing h

Pagina 83

SiEBE04-507 Outdoor UnitRemoval Procedure 1635Loosen the 4 screws to remove the fan motor. M4×16 DC fan motor6Loosen the 2 screws to remove the fan

Pagina 84 - Fit the key

Outdoor Unit SiEBE04-507164 Removal Procedure4. Remove the right side panel.1Loosen the 2 screws on the rear side.2Loosen the 3 screws on the right si

Pagina 85 - [ Replacement]

SiEBE04-507 Outdoor UnitRemoval Procedure 165 When reassembling, make sure to fit the hook.StepProcedure Points(R3257)Hook

Pagina 86 - Before a long idle period

Outdoor Unit SiEBE04-507166 Removal Procedure2.2 Removal of Electrical BoxProcedure Warning Be sure to wait 10 minutes or more after turning off all p

Pagina 87 - 2.12 Troubleshooting

SiEBE04-507 Outdoor UnitRemoval Procedure 1674Release the discharge pipe thermistor. Pay attention so as not to lose the clip for thermistor.5Release

Pagina 88 - Check again

Outdoor Unit SiEBE04-507168 Removal Procedure2.3 Removal of Reactor and Partition PlateProcedure Warning Be sure to wait 10 minutes or more after turn

Pagina 89 - Disposal requirements

SiEBE04-507 Outdoor UnitRemoval Procedure 1692The partition plate has a hook on the lower side. Lift and pull the partition plate to remove. When rea

Pagina 90 - Fault diagnosis

Specifications SiEBE04-5078 Specifications230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addit

Pagina 91 - Service Diagnosis

Outdoor Unit SiEBE04-507170 Removal Procedure2.4 Removal of Sound BlanketProcedure Warning Be sure to wait 10 minutes or more after turning off all po

Pagina 92 - 1. Caution for Diagnosis

SiEBE04-507 Outdoor UnitRemoval Procedure 1714Pull the sound blanket (inner) out. Since the piping ports on the sound blanket are torn easily, remove

Pagina 93

Outdoor Unit SiEBE04-507172 Removal Procedure2.5 Removal of Four Way ValveProcedure Warning Be sure to wait 10 minutes or more after turning off all p

Pagina 94 - 3. S ervice Check Functi on

SiEBE04-507 Outdoor UnitRemoval Procedure 1733Remove the sheets of putty.Cut the pipe with a tube cutter.4Heat up the brazed part and withdraw the pip

Pagina 95 - →See 7.)

Outdoor Unit SiEBE04-507174 Removal Procedure2.6 Removal of CompressorProcedure Warning Be sure to wait 10 minutes or more after turning off all power

Pagina 96 - → Refer to page 87.)

SiEBE04-507 Outdoor UnitRemoval Procedure 175StepProcedure Points3Heat up the brazed part of the suction side and disconnect.4Lift the compressor up a

Pagina 97 - 4. Troubleshooting

Outdoor Unit SiEBE04-507176 Removal Procedure2.7 Removal of PCBProcedure Warning Be sure to wait 10 minutes or more after turning off all power suppli

Pagina 98 -  Faulty connector connection

SiEBE04-507 Outdoor UnitRemoval Procedure 1774Loosen the 4 screws.5Undo the 3 hooks on the upper side.6Lift and pull out the PCB.StepProcedure Points(

Pagina 99 - Service Diagnosis 89

Outdoor Unit SiEBE04-507178 Removal Procedure7Feature of the PCBS70: fan motorS80: four way valveS90: thermistor (outdoor air, heat exchanger, dischar

Pagina 100 - Troubleshooting

SiEBE04-507Others 179Part 8Others1. Others ...1801.1 Tes

Pagina 101 - Service Diagnosis 91

SiEBE04-507 SpecificationsSpecifications 91.2 Heat Pump230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Am

Pagina 102

Others SiEBE04-507180 Others1. Others1.1 Test Run from the Remote ControllerFor Heat pump In cooling mode, select the lowest programmable temperature;

Pagina 103 - Service Diagnosis 93

SiEBE04-507 OthersOthers 1811.2 Jumper Settings1.2.1 When Two Units are Installed in One RoomWhen two indoor units are installed in one room, the two

Pagina 104 - 94 Service Diagnosis

Others SiEBE04-507182 Others

Pagina 105 - Service Diagnosis 95

SiEBE04-507Appendix 183Part 9Appendix1. Piping Diagrams...1841.1 Indoor

Pagina 106 - 96 Service Diagnosis

Piping Diagrams SiEBE04-507184 Appendix1. Piping Diagrams1.1 Indoor UnitsFTK(X)S20/25/35DVMW(L), FTK(X)S20/25/35DVMW9, FTK(X)S20/25/35D2VMW(L) FIELD P

Pagina 107 - Service Diagnosis 97

SiEBE04-507 Piping DiagramsAppendix 1851.2 Outdoor Units1.2.1 Cooling OnlyRKS20/25DVMB, RKS20/25D2VMBRKS35DVMB, RKS35D2VMBM3D047317MUFFLER7.9CuT7.9CuT

Pagina 108 - 4.10 Compressor Lock

Piping Diagrams SiEBE04-507186 Appendix1.2.2 Heat PumpRXS20/25DVMB, RXS20/25D2VMBRXS35DVMB, RXS35D2VMBM3D047315ACCUMULATOR9.5CuTMUFFLER9.5CuTFIELD PIP

Pagina 109 - 4.11 DC Fan Lock

SiEBE04-507 Wiring DiagramsAppendix 1872. Wiring Diagrams2.1 Indoor UnitsFTK(X)S20/25/35DVMBW(L), FTK(X)S20/25/35DVMW9, FTK(X)S20/25/35D2VMW(L)2.2 Out

Pagina 110 - 100 Service Diagnosis

Wiring Diagrams SiEBE04-507188 Appendix

Pagina 111 - Service Diagnosis 101

SiEBE04-507Index iIndexNumerics00 ...873-minutes standby ...

Pagina 112

SiEBE04-507Inverter PairWall Mounted Type D-Series Ser viceManual[Applied Models]zInverter Pair : Cooling OnlyzInverter Pair : Heat Pump

Pagina 113 - Service Diagnosis 103

Specifications SiEBE04-50710 Specifications230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addi

Pagina 114 - 104 Service Diagnosis

SiEBE04-507ii IndexL4 ...113L5 ...

Pagina 115

SiEBE04-507Index iiiPP4 ...109partition plate ...

Pagina 117 - Service Diagnosis 107

SiEBE04-507Drawings & Flow Charts vDrawings & Flow ChartsAARC433A ...84automatic a

Pagina 118 - 108 Service Diagnosis

SiEBE04-507vi Drawings & Flow ChartsTtarget discharge pipe temperature control ...48thermistor or related abnormality (indoor unit) ...

Pagina 119 - P4, J3, J6, H9

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (

Pagina 120

SiEBE04-507 SpecificationsSpecifications 11230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addi

Pagina 121 - Service Diagnosis 111

Specifications SiEBE04-50712 Specifications230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addi

Pagina 122

SiEBE04-507 SpecificationsSpecifications 13230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addi

Pagina 123 - Service Diagnosis 113

Specifications SiEBE04-50714 Specifications230V, 50HzNotes:  MAX. interunit piping length: 20m MAX. interunit height difference: 15m Amount of addi

Pagina 124

SiEBE04-507Printed Circuit Board Connector Wiring Diagram 15Part 3Printed Circuit BoardConnector Wiring Diagram1. Printed Circuit Board Connector Wiri

Pagina 125 - Service Diagnosis 115

Printed Circuit Board Connector Wiring Diagram SiEBE04-50716 Printed Circuit Board Connector Wiring Diagram1. Pri nted Circui t Board Connector Wiri n

Pagina 126

SiEBE04-507 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 17PCB Detail PCB(1): Control PCBPCB(4): INTEL

Pagina 127 - 4.23 Insufficient Gas

Printed Circuit Board Connector Wiring Diagram SiEBE04-50718 Printed Circuit Board Connector Wiring Diagram1.2 Outdoor UnitConnectorsNote: Other desig

Pagina 128

SiEBE04-507 Printed Circuit Board Connector Wiring DiagramPrinted Circuit Board Connector Wiring Diagram 19PCB Detail PCB(1): Filter PCBPCB(2): Contro

Pagina 129 - 4.24 Over-voltage Detection

SiEBE04-507Table of Contents iInverter PairD-SerieszCooling OnlyIndoor UnitFTKS20DVMW(L) FTKS20DVMW9 FTKS20D2VMW(L)FTKS25DVMW(L) FTKS25DVMW9 FTKS25D2V

Pagina 130 - 5. Check

Printed Circuit Board Connector Wiring Diagram SiEBE04-50720 Printed Circuit Board Connector Wiring Diagram

Pagina 131 - Check No.5

SiEBE04-507Function and Control 21Part 4 Function and Control1. Main Functions...

Pagina 132 - (R25 = 20k⍀, B = 3950)

Main Functions SiEBE04-50722 Function and Control1. Main FunctionsNote:See the list of functions for the functions applicable to different models.1.1

Pagina 133 - Check No.8

SiEBE04-507 Main FunctionsFunction and Control 23Inverter Features The inverter provides the following features: The regulating capacity can be chang

Pagina 134 - Check No.11

Main Functions SiEBE04-50724 Function and Control1.2 Air Flow Direction ControlPower-AirflowDual FlapsThe large flaps send a large volume of air downw

Pagina 135 - 5.1.10 Power Transistor Check

SiEBE04-507 Main FunctionsFunction and Control 251.3 Fan Speed Control for Indoor UnitsControl Mode The airflow rate can be automatically controlled d

Pagina 136 - 126 Service Diagnosis

Main Functions SiEBE04-50726 Function and Control1.4 Programme Dry FunctionProgramme dry function removes humidity while preventing the room temperatu

Pagina 137 - Removal Procedure

SiEBE04-507 Main FunctionsFunction and Control 271.5 Automatic OperationAutomatic Cooling / Heating Function (Heat Pump Only)When the AUTO mode is sel

Pagina 138 - 1. Indoor Unit

Main Functions SiEBE04-50728 Function and Control1.6 Thermostat ControlThermostat control is based on the difference between the room temperature and

Pagina 139 - Titanium apatite

SiEBE04-507 Main FunctionsFunction and Control 291.7 NIGHT SET ModeWhen the OFF timer is set, the NIGHT SET circuit automatically activates.The NIGHT

Pagina 140 - 1.2 Removal of Front Panel

SiEBE04-507ii Table of Contents1. Introduction ...v1.1 Safet

Pagina 141 - Step Procedure Points

Main Functions SiEBE04-50730 Function and Control1.8 ECONO ModeOutline The "ECONO mode" reduces the maximum operating current and power cons

Pagina 142 - 1.3 Removal of Front Grille

SiEBE04-507 Main FunctionsFunction and Control 311.9 INTELLIGENT EYEThis is the function that detects existence of humans in the room by a human motio

Pagina 143

Main Functions SiEBE04-50732 Function and Control Since the set temperature is shifted by 2°C higher for 40 minutes, compressor speed becomes low and

Pagina 144 - Section View

SiEBE04-507 Main FunctionsFunction and Control 331.10 Inverter POWERFUL OperationOutline In order to exploit the cooling and heating capacity to full

Pagina 145 - Horizontal blade (small)

Main Functions SiEBE04-50734 Function and Control1.11 Other Functions1.11.1 Hot Start FunctionHeat Pump OnlyIn order to prevent the cold air blast tha

Pagina 146

SiEBE04-507 Function of ThermistorFunction and Control 352. Function of Thermistor2.1 Heat Pump ModelA Outdoor Heat ExchangerThermistor (DCB)1. The

Pagina 147

Function of Thermistor SiEBE04-50736 Function and Control2.2 Cooling Only ModelA Outdoor Heat ExchangerThermistor (DCB)1. The outdoor heat exchanger

Pagina 148 - 1.5 Removal of Electrical Box

SiEBE04-507 Control SpecificationFunction and Control 373. Control Specification3.1 Mode HierarchyOutline There are two modes; the mode selected in us

Pagina 149

Control Specification SiEBE04-50738 Function and Control3.2 Frequency ControlOutline Frequency will be determined according to the difference between

Pagina 150

SiEBE04-507 Control SpecificationFunction and Control 392. Determine upper limit frequency Set a minimum value as an upper limit frequency among the

Pagina 151 - 1.6 Removal of PCB

SiEBE04-507Table of Contents iiiPart 5 System Configuration... 531. System Configuration...

Pagina 152

Control Specification SiEBE04-50740 Function and Control3.3 Controls at Mode Changing / Start-up3.3.1 Preheating OperationOutline Operate the inverter

Pagina 153

SiEBE04-507 Control SpecificationFunction and Control 413.3.4 3-minutes StandbyProhibit to turn ON the compressor for 3 minutes after turning it off.(

Pagina 154 - INTELLIGENT EYE

Control Specification SiEBE04-50742 Function and Control3.5 Input Current ControlOutline The microcomputer calculates the input current during the com

Pagina 155

SiEBE04-507 Control SpecificationFunction and Control 433.6 Freeze-up Protection ControlOutline During cooling operation, the signals being sent from

Pagina 156 - 146 Removal Procedure

Control Specification SiEBE04-50744 Function and Control3.8 Fan ControlOutline Fan control is carried out with following functions.1. Fan control when

Pagina 157 - 1.7 Removal of Drain Pan Unit

SiEBE04-507 Control SpecificationFunction and Control 453.10 Defrost ControlOutline Heat Pump OnlyDefrosting is carried out by the cooling cycle (reve

Pagina 158 - Swing motor

Control Specification SiEBE04-50746 Function and Control3.11 Electronic Expansion Valve ControlOutline The following items are included in the electro

Pagina 159 - Drain hose

SiEBE04-507 Control SpecificationFunction and Control 473.11.1 Fully Closing with Power ONInitialize the electronic expansion valve when turning on th

Pagina 160 - (Right side)

Control Specification SiEBE04-50748 Function and Control3.11.7 Control when frequency is changedWhen the target discharge pipe temperature control is

Pagina 161 - 1.8 Removal of Fan Motor

SiEBE04-507 Control SpecificationFunction and Control 493.12 Malfunctions3.12.1 Sensor Malfunction DetectionSensor malfunction may occur in the thermi

Pagina 162 - Remove the fan motor

SiEBE04-507iv Table of ContentsPart 7 Removal Procedure ... 1271. Indoor Unit...

Pagina 163 - 1.9 Removal of Heat Exchanger

Control Specification SiEBE04-50750 Function and ControlDetail I Judgment by power consumptionWhen an output frequency is exceeds 55 Hz and the input

Pagina 164 - Lower hook

SiEBE04-507 Control SpecificationFunction and Control 513.15 Facility Setting Jumper (cooling at low outdoor temperature)Outline This function is limi

Pagina 165 - Hook (right)

Control Specification SiEBE04-50752 Function and Control

Pagina 166 - 1.10 Removal of Fan Rotor

SiEBE04-507System Configuration 53Part 5System Configuration1. System Configuration...

Pagina 167

System Configuration SiEBE04-50754 System Configuration1. System ConfigurationAfter the installation and test operation of the room air conditioner ha

Pagina 168

SiEBE04-507 InstructionSystem Configuration 552. Instruction2.1 Safety precautions• Keep this manual where the operator can easily find them.• Read th

Pagina 169 - 2. Outdoor Unit

Instruction SiEBE04-50756 System Configuration• Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid injury, do not r

Pagina 170 - Front panel

SiEBE04-507 InstructionSystem Configuration 572.2 Names of partsIndoor UnitON/OFF16 141315124315791011862

Pagina 171 - Propeller fan

Instruction SiEBE04-50758 System ConfigurationOutdoor Unit192220211817 Indoor Unit Outdoor Unit 1. Air filter 2. Titanium Apatite Photocatalytic Ai

Pagina 172 - Procedure Points

SiEBE04-507 InstructionSystem Configuration 59TEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFF125691012111618171315143478 Remo

Pagina 173 - Removal Procedure 163

SiEBE04-507 Introductionv1. Introduction1.1 Safety CautionsCautions and Warnings Be sure to read the following safety cautions before conducting repa

Pagina 174 - Right side panel

Instruction SiEBE04-50760 System Configuration2.3 Preparation before Operation+––+231Position + and – correctly!To set the batteries1. Press

Pagina 175 -  When reassembling, make

SiEBE04-507 InstructionSystem Configuration 61ReceiverSet.To remove, pull it upwards.Remote controller holderTo operate the remote controllerTo fix

Pagina 176 - 2.2 Removal of Electrical Box

Instruction SiEBE04-50762 System ConfigurationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFF1.32To set the clock1. Press “

Pagina 177

SiEBE04-507 InstructionSystem Configuration 632.4 AUTO · DRY · COOL · HEAT · FAN OperationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTI

Pagina 178 - 168 Removal Procedure

Instruction SiEBE04-50764 System Configuration To change the ai r flow rate setting5. Press “FAN setting button”.DRY modeThe air flow rate

Pagina 179 - Removal Procedure 169

SiEBE04-507 InstructionSystem Configuration 652.5 Adjusting the Air Flow DirectionTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANC

Pagina 180 - 2.4 Removal of Sound Blanket

Instruction SiEBE04-50766 System Configuration5°In DRY mode or COOL modeIn HEAT modeWhen stop operationUpper limitLower limit10°50°30°65°When stop o

Pagina 181 - Removal Procedure 171

SiEBE04-507 InstructionSystem Configuration 672.6 POWERFUL OperationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFFPOWERFUL

Pagina 182 - 2.5 Removal of Four Way Valve

Instruction SiEBE04-50768 System Configuration2.7 OUTDOOR UNIT SILENT OperationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCEL

Pagina 183 - Removal Procedure 173

SiEBE04-507 InstructionSystem Configuration 692.8 ECONO OperationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFF1, 2ECONO op

Pagina 184 - 2.6 Removal of Compressor

Introduction SiEBE04-507vi1.1.2 Cautions Regarding Products after RepairDo not repair the electrical components with wet hands.Working on the equipmen

Pagina 185 - Lift the compressor up

Instruction SiEBE04-50770 System Configuration2.9 INTELLIGENT EYE Operation [EX.]TEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCEL

Pagina 186 - 2.7 Removal of PCB

SiEBE04-507 InstructionSystem Configuration 7190°55°7m55°7m“INTELLIGENT EYE” is useful for EnergySavingNotes on “INTELLIGENT EYE” Energysaving operat

Pagina 187 - Lift and pull out the

Instruction SiEBE04-50772 System Configuration2.10 TIMER OperationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFF421, 3Timer

Pagina 188 - 178 Removal Procedure

SiEBE04-507 InstructionSystem Configuration 73TEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFF21, 34Display(Example)Combined

Pagina 189 - Others 179

Instruction SiEBE04-50774 System Configuration2.11 Care and CleaningUnitsCAUTIONBefore cleaning, be sure to stop the operation and turn the breaker

Pagina 190 - 1. Others

SiEBE04-507 InstructionSystem Configuration 75[ Maintenance ][ Replacement]Air filterPushFilters1. Open the front panel. (page 23.)2. Pull out the

Pagina 191 - 1.2 Jumper Settings

Instruction SiEBE04-50776 System ConfigurationNOTE• Operation with dirty filters: (1) cannot deodorize the air. (2) cannot clean the air. (3) results

Pagina 192 - 182 Others

SiEBE04-507 InstructionSystem Configuration 772.12 TroubleshootingThese cases are not troubles.The following casesare not air conditioner troublesbut

Pagina 193 - Appendix

Instruction SiEBE04-50778 System ConfigurationCheck again.Please check again before calling a repair person.CaseCheckThe air conditioner does not oper

Pagina 194 - 1. Piping Diagrams

SiEBE04-507 InstructionSystem Configuration 79Call the service shop immediately.WARNING When an abnormality (such as a burning smell) occurs, stop op

Pagina 195 - 1.2 Outdoor Units

SiEBE04-507 Introductionvii1.1.3 Inspection after RepairBe sure to use the specified cable to connect between the indoor and outdoor units. Make the c

Pagina 196 - 1.2.2 Heat Pump

Instruction SiEBE04-50780 System ConfigurationTEMPON/OFFPOWERFULMODEFA NSWINGSILENTSENSORECONOCOMFORTTIMERONCANCELOFFFault diagnosis.FAULT DIAGNOSIS B

Pagina 197 - 2. Wiring Diagrams

SiEBE04-507Service Diagnosis 81Part 6Service Diagnosis1. Caution for Diagnosis...

Pagina 198 - 188 Appendix

Caution for Diagnosis SiEBE04-50782 Service Diagnosis1. Caution for DiagnosisThe operation lamp flashes when any of the following errors is detected.1

Pagina 199

SiEBE04-507 Problem Symptoms and MeasuresService Diagnosis 832. Problem Symptoms and MeasuresSymptom Check Item Details of MeasureReferencePageNone of

Pagina 200

Service Check Function SiEBE04-50784 Service Diagnosis3. S ervice Check Functi onIn the ARC433A series remote controller, the temperature display sect

Pagina 201 - Index iii

SiEBE04-507 Service Check FunctionService Diagnosis 85Check Method 21. Enter the diagnosis mode.Press the 3 buttons (TEMPs,TEMPt, MODE) simultaneously

Pagina 202

Service Check Function SiEBE04-50786 Service Diagnosis5. Press the TEMP button.Press TEMPs or TEMPt and change the digit until you hear the sound of “

Pagina 203 - Drawings & Flow Charts

SiEBE04-507 TroubleshootingService Diagnosis 874. Troubleshooting4.1 Error Codes and DescriptionH: Displayed only when system-down occurs.Code Indicat

Pagina 204

Troubleshooting SiEBE04-50788 Service Diagnosis4.2 Indoor Unit PCB AbnormalityRemoteControllerDisplayA1Method of Malfunction DetectionEvaluation of ze

Pagina 205 - B-8400 Ostend - Belgium

SiEBE04-507 TroubleshootingService Diagnosis 894.3 Freeze-up Protection Control or High Pressure ControlRemoteControllerDisplayA5Method of Malfunction

Commenti su questo manuale

Nessun commento