DAIKIN ROOM AIR CONDITIONER
INSTALLATION MANUAL
R410A Split Series
EnglishDeutschFrançaisNederlandsEspañolItalianoEλληνικάPortuguesPyccкийТürkçe
Installation manual
Installationsanleitung
Manuel d’installation
Installatiehandleiding
Manual de instalación
Manuale di installazione
Εγχειρίδιο εγκατάστασης
Manual de instalação
Руководство по монтажу
Montaj kılavuzları
MODELS
FVXG25K2V1B
FVXG35K2V1B
FVXG50K2V1B
00_CV_3P276870-1.indd 100_CV_3P276870-1.indd 1 12/7/2010 2:54:36 PM12/7/2010 2:54:36 PM
Vedere la pagina 0
1 2 3 4 5 6 ... 26 27

Sommario

Pagina 1 - INSTALLATION MANUAL

DAIKIN ROOM AIR CONDITIONERINSTALLATION MANUALR410A Split SeriesEnglishDeutschFrançaisNederlandsEspañolItalianoEλληνικάPortuguesPyccкийТürkçeInstallat

Pagina 2 - Low Voltage 2006/95/EC

English 6EnglishWhen connecting to an HA system5. Take out the terminal block and electrical wiring box, and open the lid for the electrical wiring

Pagina 3 - 3SB64417-16L

7 EnglishIndoor Unit Installation PatternsThe indoor unit can not be installed at a position where it directly comes in contact with the fl oor.• The

Pagina 4

English 8EnglishIndoor Unit Installation DrawingsBe sure to install the indoor unit in accordance with the installation instructions below for any i

Pagina 5 - Safety Precautions

9 EnglishIndoor Unit InstallationExposed installationInstalling the mounting plate1. Decide the installation site with reference to the descriptions

Pagina 6 - Choosing an Installation Site

English 10EnglishRefrigerant piping2. Create a hole in the refrigerant piping in accordance with the conditions shown in the illustration.• The loca

Pagina 7 - Installation Tips

11 EnglishIndoor Unit InstallationShaping the refrigerant pipe4. Form the shape of the refrigerant pipe in accordance with the restric-• tions shown

Pagina 8

English 12EnglishInstalling the indoor unit on the mounting plate5. Remove the front panel and front grille.1) Insert the 2) C drain hose into the s

Pagina 9

13 EnglishIndoor Unit InstallationOpen the fl ap.5) Remove the air outlet cover.6) 6)-1. Remove the air outlet cover while lifting the 3 tabs on the

Pagina 10 - English 6

English 14EnglishRemove the fi xing screws (2 pcs.), press the tabs (3 positions) using a fl athead screwdriver, and remove the upper 7) casing.Remove

Pagina 11 - CAUTION

15 EnglishIndoor Unit InstallationConnecting the drain hose to the VP pipe, and hanging the indoor unit on the mount-ing plateUse commercial rigid p

Pagina 12 - English 8

Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan DAIKIN INDUSTRIES, LTD.Low Voltage 2006/95/ECElectromagnetic Compatibility 2

Pagina 13 - Indoor Unit Installation

English 16EnglishRefrigerant Piping WorkRemoving the drip proof cover1. Take out 1 screw and remove the drip proof cover.• HookTabUse the holding ta

Pagina 14 - Refrigerant piping2

17 EnglishRefrigerant Piping WorkRefrigerant piping3. CAUTIONUse the fl are nut fi xed to the main unit. (To prevent cracking of the fl are nut by ag

Pagina 15

English 18EnglishPurging air4. For the air purging procedures, please refer to the outdoor unit’s installation manual.• Checking for gas leakage5. W

Pagina 16 - For side piping

19 EnglishWiringOpen the service lid.1) Strip wire ends (15mm).2) Match wire colours with terminal numbers on indoor and outdoor unit’s terminal blo

Pagina 17

English 20EnglishHalf Concealed InstallationOnly items peculiar to this installation method are given here. See Exposed Installation for additional

Pagina 18

21 EnglishHalf Concealed InstallationRefrigerant piping3. Refer to Shaping the refrigerant pipe (page 11) for details.• 10510540404540Left bottom pi

Pagina 19

English 22EnglishTrial Operation and TestingTrial operation and testing1. Measure the supply voltage and make sure that it falls in the specifi ed ra

Pagina 20 - Refrigerant Piping Work

Two-dimensional bar code is a code for manufacturing.3P276870-1 M10B206(1104) HT00_CV_3P276870-1.indd 200_CV_3P276870-1.indd 2 12/7/2010 2:54:37

Pagina 21

Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan , ,FVXG25K2V1B, FVXG35K2V1B, FVXG50K2V1B3SB64417-16LShinri SadaMa

Pagina 22 - Checking for gas leakage5

3SB64417-16L.fm Page 2 Wednesday, February 16, 2011 10:51 AM

Pagina 23 - WARNING

1 EnglishSafety PrecautionsThe precautions described herein are classifi ed as WARNING and CAUTION. They both contain important informa-• tion regard

Pagina 24 - Half Concealed Installation

English 2EnglishAccessories Indoor unit A – KA Mounting plate1E Wireless remote controller1J Operation manual1B Titanium apatite photocata-lyt

Pagina 25

3 EnglishInstallation TipsRemoving and installing front panel1. Removal method• Slide the front panel stoppers on both sides upward, 1) and open the

Pagina 26 - Trial Operation and Testing

English 4EnglishRemoving and installing air fi lters2. Removal method• Open the front panel.1) Remove both air fi lters (upper).2) Remove both air fi l

Pagina 27 - (1104) HT

5 EnglishInstallation TipsHow to set the different addresses4. When two indoor units are installed in one room, the two wireless remote controllers