Daikin BRC7E65 Specifiche Pagina 152

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 151
Si38-606 Troubleshooting by Indication on the Remote Controller
Troubleshooting 141
1: Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
{
: Continuity
×: No continuity
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × {
Approx.
300
× {
Approx.
150
×
2. Yellow × {
Approx.
300
× {
Approx.
150
3. Orange × {
Approx.
150
×
4. Blue × {
Approx.
150
5. Red ×
6. Brown
Vedere la pagina 151
1 2 ... 147 148 149 150 151 152 153 154 155 156 157 ... 253 254