INSTALLATION MANUALIII SYSTEM Air ConditionersMODELS〈BS unit〉 BSVQ36PVJUBSVQ60PVJUBSVQ96PVJUEnglishFrançaisEspañolRead these instructions carefully be
9 English6-3 PIPING CONNECTION WORK PRECAUTIONS• When brazing refrigerant piping, begin working after replacing the nitrogen (*1) or perform brazing w
English 10Table 1 Indoor unit total capacity and pipe sizeTable 2 Indoor unit connection pipe size* The BS unit downstream connection pipe sizes a
11 EnglishSuction gas pipe (Site piping)HP/LP gas pipe (Site piping)Gas pipe (Site piping)Liquid pipe (Site piping)Liquid pipe (Site piping)BS unit(To
English 126-6 PIPING INSULATION• After the gas leak inspection is completed, refer to the following figures and use the included insulation tube 3) an
13 English7. ELECTRIC WIRING WORK7-1 GENERAL INSTRUCTIONS• All wiring must be performed by an authorized electrician.• All field supplied parts and ma
English 14Table 3 MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)NOTES• The above Table 3 of Electrical Characteristics refers to one BS unit.• S
15 English7-5 WIRING CONNECTIONSRemove the Electrical Components Box lid on the side and follow the directions to connect the wires.〈Transmission wiri
English 16NOTES• Use ring-type crimp style terminal for connections to the power terminal block. (Refer to Fig. 6)Also, insulate the crimped area by a
17 English〈Setting description〉• The “Automatic mode differential” can be changed within the range of 0°F to 12.6°F (0°F at factory ship-ment).• For d
3P194121-3M EM07A062C(0909) FS
1 EnglishBSVQ36PVJUBSVQ60PVJUBSVQ96PVJUVRVIII SYSTEM Air ConditionersInstallation manualCONTENTS1 SAFETY CONSIDERATIONS...
English 2• After completing the installation work, check that the refrigerant gas does not leak throughout the system.• Do not install unit in an area
3 English• Install drain piping to proper drainage. Improper drain piping may result in water leakage and prop-erty damage.• Insulate piping to preven
English 4NOTEThe refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.A. Clean and dryForeign materials (including m
5 English2-4 COMBINATION• This BS unit is only for systems for Models P series.It cannot be connected to systems for Models M series.• For series of a
English 6Note: The Electrical Components Box mounting surface can be changed.For information on how to change the mounting surface, refer to “5. BS UN
7 English5. BS UNIT INSTALLATIONUse only accessories and parts which are of the designated specification when installing.(1)When necessary, use the fo
English 86. REFRIGERANT PIPING WORK• For instruction for installing piping between the outside unit and BS unit, selecting a refrigerant branch kit, a